STEEL HEATING CONVECTORS

With a double on the vertical heat exchanger

WITH MOUNTING ON BRACKETS OR ON SUPPORTS

  • The devices are designed for mounting on the walls with uneven surfaces or in the conditions when the device can not be installed right up to the wall because of fittings and tubes. The convectors can also be installed by means of special supports (they are supplied separately) on the floor surface.
  • Effective operation of the convectors when they are installed at a distance from the wall is ensured by the rear panel presence.
  • The nomenclature presents the devices of customary and antivandal  modification of the case

.

 

 

Heat carrier working temperature – up to up to 110  ̊C

Heat carrier excessive working pressure – up to 1,6 MPa

Excessive test pressure – 2,4 MPa

Ultimate strength – not less than 6,0 MPa

Connection – G1/2 (internal thread)

Complete set: steel convector, installation kit (in separate package), operations manual. Supports for installing on the floor are delivered by a separate order.

Technical characteristics of the heating convectors

          Model          Height, cm Length, cm Depth, cm Distance between centres, cm Volume of the heat carrier, not over, dm3 Mass without the heat carrier, not over, kg
КСК-2 40/30 НБ 2В, НБАВ 2В 41 36 8,5 9,0 0,34 5,4
КСК-2 40/40 НБ 2В, НБАВ 2В 45 0,42 6,8
КСК-2 40/60 НБ 2В, НБАВ 2В 65 0,58 9,5
КСК-2 40/80 НБ 2В, НБАВ 2В 85 0,75 12,2
КСК-2 40/100 НБ 2В, НБАВ 2В 105 0,9 14,9
КСК-2 40/120 НБ 2В, НБАВ 2В 124 1,06 17,7
КСК-2 40/140 НБ 2В, НБАВ 2В 143,6 1,22 20,4
КСК-2 40/160 НБ 2В, НБАВ 2В 163,2 1,38 23,1
КСК-2 40/180 НБ 2В, НБАВ 2В 183 1,74 25,8
КСК-2 40/200 НБ 2В, НБАВ 2В 202,5 1,92 28,5

Rated heat flow of the heating convectors at different values of the thermal head

           Model       

Rated thermal head (heat rate), kW

30ºС (55/45/20)*

42,5ºС (70/55/20)

45ºС (70/60/20)

50ºС (75/65/20)

60ºС (90/70/20)

70ºС (95/85/20)

КСК-2 40/30 НБ 2В, НБАВ 2В 0,16 0,22 0,24 0,28 0,35 0,43
КСК-2 40/40 НБ 2В, НБАВ 2В 0,25 0,33 0,36 0,42 0,52 0,64
КСК-2 40/60 НБ 2В, НБАВ 2В 0,38 0,51 0,55 0,63 0,8 0,98
КСК-2 40/80 НБ 2В, НБАВ 2В 0,51 0,69 0,74 0,86 1,08 1,32
КСК-2 40/100 НБ 2В, НБАВ 2В 0,66 0,89 0,96 1,11 1,4 1,71
КСК-2 40/120 НБ 2В, НБАВ 2В 0,81 1,09 1,17 1,35 1,7 2,08
КСК-2 40/140 НБ 2В, НБАВ 2В 0,95 1,29 1,39 1,59 2,02 2,46
КСК-2 40/160 НБ 2В, НБАВ 2В 1,09 1,48 1,59 1,84 2,32 2,83
КСК-2 40/180 НБ 2В, НБАВ 2В 1,24 1,67 1,81 2,08 2,62 3,20
КСК-2 40/200 НБ 2В, НБАВ 2В 1,39 1,88 2,03 2,34 2,95 3,60

* - thermal heat value at the devices inlet and outlettemperature 55̊ C and 45̊ C correspondingly and at the air temperature in the heating room 20̊ C. This determination of the thermal head is valid and for its other values.

Conventional designations:

КСК/хх – steel heating convector «Термія» with wall mounting on brackets, with double on the vertical heat exchanger (2B), where xx – device length, y – modification variant.

Convectors modification variants according to their connection are designated by the following indexes:

НБ – lower lateral;

НБ, АВ - lower lateral, antivandal modification.